A care home does not evacuate the way an office does. Residents move sideways into the next fire compartment rather than out of the building, which means the compartment has to hold for as long as it takes to move people who cannot move themselves. Every door in that line is part of the structure, not a piece of joinery. The doors are the part everyone inspects. The penetrations above the ceiling, where cables and pipes cross the compartment wall, are the part that fails.
What to specify
What fails in a care home
Compliant products
Product listings in preparation
Every product listed here will carry a verified specification and a current price band. Nothing appears until both have been confirmed, so what you read can be relied on when you specify.
Testing cadence
What has to happen, and how often
Staff visual check
MonthlyDoes it close and latch from any angle, is anything wedging it, is the signage there. Twenty seconds a door and it catches most of what goes wrong.
Competent person inspection
Six monthlyGaps measured, seals examined, closer force checked, ironmongery confirmed as rated. The fire risk assessment sets the interval, and six monthly is the accepted position for a care setting.
Hold open device test
Weekly, with the alarm testEvery electromagnetic hold open must release and the door must close fully when the alarm sounds. Test it as part of the weekly alarm test, not separately.
Compartmentation survey
On any alteration, and reviewed with the fire risk assessmentAbove the ceiling and inside the risers. Every new cable, pipe or duct through a compartment wall is a breach until it is fire stopped and recorded.
Standards
BS 476-22:1987
Fire resistance of non loadbearing elements, the UK test method
BS EN 1634-1
Fire resistance tests for door and shutter assemblies, the European method
BS EN 13501-2
Fire classification from resistance test data
BS 8214:2016
Code of practice for timber based fire door assemblies
BS EN 1154
Controlled door closing devices
BS EN 1155
Electrically powered hold open devices
Enforced by the fire and rescue authority under the Regulatory Reform (Fire Safety) Order 2005. The responsible person must keep fire doors under suitable maintenance and be able to evidence it. CQC looks at premises safety alongside it.